UPSMON(8)			  NUT Manual			     UPSMON(8)

NAME
       upsmon -	UPS monitor and	shutdown controller

SYNOPSIS
       upsmon -h

       upsmon -c command

       upsmon [-D] [-K]	[-p] [-u user]

DESCRIPTION
       upsmon is the client process that is responsible	for the	most important
       part of UPS monitoring--shutting	down the system	when the power goes
       out. It can call	out to other helper programs for notification purposes
       during power events.

       upsmon can monitor multiple systems using a single process. Every UPS
       that is defined in the upsmon.conf(5) configuration file	is assigned a
       power value and a type (primary or secondary).

OPTIONS
       -h
	   Display the help message.

       -c command
	   Send	the command command to the existing upsmon process. Valid
	   commands are:

	   fsd
	       shutdown	all primary-mode UPSes (use with caution)

	   stop
	       stop monitoring and exit

	   reload
	       reread upsmon.conf(5) configuration file. See "reloading
	       nuances"	below if this doesn't work.

       -D
	   Raise the debugging level. upsmon will run in the foreground	and
	   prints information on stdout	about the monitoring process. Use this
	   multiple times for more details.

       -K
	   Test	for the	shutdown flag. If it exists and	contains the magic
	   string from upsmon, then upsmon will	exit with EXIT_SUCCESS.	Any
	   other condition will	make upsmon exit with EXIT_FAILURE.

	   You can test	for a successful exit from upsmon -K in	your shutdown
	   scripts to know when	to call	upsdrvctl(8) to	shut down the UPS.

       -p
	   Run privileged all the time.	Normally upsmon	will split into	two
	   processes. The majority of the code runs as an unprivileged user,
	   and only a tiny stub	runs as	root. This switch will disable that
	   mode, and run the old "all root all the time" system.

	   This	is not the recommended mode, and you should not	use this
	   unless you have a very good reason.

       -u user
	   Set the user	for the	unprivileged monitoring	process. This has no
	   effect when using -p.

	   The default user is set at configure	time with configure
	   --with-user=.... Typically this is nobody, but other	distributions
	   will	probably have a	specific nut user for this task. If your
	   notification	scripts	need to	run as a specific user,	set it here.

	   You can also	set this in the	upsmon.conf(5) file with the
	   RUN_AS_USER directive.

UPS DEFINITIONS
       In the upsmon.conf(5), you must specify at least	one UPS	that will be
       monitored. Use the MONITOR directive.

	   MONITOR 'system' 'powervalue' 'username' 'password' 'type'

       The system refers to a upsd(8) server, in the form
       upsname[@hostname[:port]]. The default hostname is "localhost". Some
       examples	follow:

       o   "su700@mybox" means a UPS called "su700" on a system	called
	   "mybox". This is the	normal form.

       o   "fenton@bigbox:5678"	is a UPS called	"fenton" on a system called
	   "bigbox" which runs upsd(8) on port "5678".

       The powervalue refers to	how many power supplies	on this	system are
       being driven this UPS. This is typically	set to 1, but see the section
       on power	values below.

       The username is a section in your upsd.users(5) file. Whatever password
       you set in that section must match the password set in this file.

       The type	set in that section must also match the	type here -- primary
       or secondary. In	general, a primary process is one running on the
       system with the UPS actually plugged into a serial port,	and a
       secondary is drawing power from the UPS but can't talk to it directly.
       See the section on UPS types for	more.

NOTIFY EVENTS
       upsmon senses several events as it monitors each	UPS. They are called
       notify events as	they can be used to tell the users and admins about
       the change in status. See the additional	NOTIFY-related sections	below
       for information on customizing the delivery of these messages.

       ONLINE
	   The UPS is back on line.

       ONBATT
	   The UPS is on battery.

       LOWBATT
	   The UPS battery is low (as determined by the	driver).

       FSD
	   The UPS has been commanded into the "forced shutdown" mode.

       COMMOK
	   Communication with the UPS has been established.

       COMMBAD
	   Communication with the UPS was just lost.

       SHUTDOWN
	   The local system is being shut down.

       REPLBATT
	   The UPS needs to have its battery replaced.

       NOCOMM
	   The UPS can't be contacted for monitoring.

NOTIFY COMMAND
       In upsmon.conf(5), you can configure a program called the NOTIFYCMD
       that will handle	events that occur.

       NOTIFYCMD "path to program"

       NOTIFYCMD "/usr/local/bin/notifyme"

       Remember	to wrap	the path in "quotes" if	it contains any	spaces.

       The program you run as your NOTIFYCMD can use the environment variables
       NOTIFYTYPE and UPSNAME to know what has happened	and on which UPS. It
       also receives the notification message (see below) as the first (and
       only) argument, so you can deliver a pre-formatted message too.

       Note that the NOTIFYCMD will only be called for a given event when you
       set the EXEC flag by using the notify flags, below:

NOTIFY FLAGS
       By default, all notify events (see above) generate a global message
       (wall) to all users, plus they are logged via the syslog. You can
       change this with	the NOTIFYFLAG directive in the	configuration file:

       NOTIFYFLAG notifytype flags

       Examples:

       o   NOTIFYFLAG ONLINE SYSLOG

       o   NOTIFYFLAG ONBATT SYSLOG+WALL

       o   NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

       The flags that can be set on a given notify event are:

       SYSLOG
	   Write this message to the syslog.

       WALL
	   Send	this message to	all users on the system	via wall(1).

       EXEC
	   Execute the NOTIFYCMD.

       IGNORE
	   Don't do anything. If you use this, don't use any of	the other
	   flags.

       You can mix these flags.	"SYSLOG+WALL+EXEC" does	all three for a	given
       event.

NOTIFY MESSAGES
       upsmon comes with default messages for each of the NOTIFY events. These
       can be changed with the NOTIFYMSG directive.

       NOTIFYMSG type "message"

       Examples:

       o   NOTIFYMSG ONLINE "UPS %s is getting line power"

       o   ` NOTIFYMSG ONBATT "Someone pulled the plug on %s"`

       The first instance of %s	is replaced with the identifier	of the UPS
       that generated the event. These messages	are used when sending walls to
       the users directly from upsmon, and are also passed to the NOTIFYCMD.

POWER VALUES
       The "current overall power value" is the	sum of all UPSes that are
       currently able to supply	power to the system hosting upsmon. Any	UPS
       that is either on line or just on battery contributes to	this number.
       If a UPS	is critical (on	battery	and low	battery) or has	been put into
       "forced shutdown" mode, it no longer contributes.

       A "power	value" on a MONITOR line in the	config file is the number of
       power supplies that the UPS runs	on the current system.

       MONITOR upsname powervalue username password type

       Normally, you only have one power supply, so it will be set to 1.

       MONITOR myups@myhost 1 username mypassword primary

       On a large server with redundant	power supplies,	the power value	for a
       UPS may be greater than 1. You may also have more than one of them
       defined.

       MONITOR ups-alpha@myhost	2 username mypassword primary

       MONITOR ups-beta@myhost 2 username mypassword primary

       You can also set	the power value	for a UPS to 0 if it does not supply
       any power to that system. This is generally used	when you want to use
       the upsmon notification features	for a UPS even though it's not
       actually	running	the system that	hosts upsmon. Don't set	this to
       "primary" unless	you really want	to power this UPS off when this
       instance	of upsmon needs	to shut	down for its own reasons.

       MONITOR faraway@anotherbox 0 username mypassword	secondary

       The "minimum power value" is the	number of power	supplies that must be
       receiving power in order	to keep	the computer running.

       MINSUPPLIES value

       Typical PCs only	have 1,	so most	users will leave this at the default.

       MINSUPPLIES 1

       If you have a server or similar system with redundant power, then this
       value will usually be set higher. One that requires three power
       supplies	to be running at all times would simply	set it to 3.

       MINSUPPLIES 3

       When the	current	overall	power value drops below	the minimum power
       value, upsmon starts the	shutdown sequence. This	design allows you to
       lose some of your power supplies	in a redundant power environment
       without bringing	down the entire	system while still working properly
       for smaller systems.

UPS TYPES
       upsmon and upsd(8) don't	always run on the same system. When they do,
       any UPSes that are directly attached to the upsmon host should be
       monitored in "primary" mode. This makes upsmon take charge of that
       equipment, and it will wait for the "secondary" systems to disconnect
       before shutting down the	local system. This allows the distant systems
       (monitoring over	the network) to	shut down cleanly before upsdrvctl
       shutdown	runs and turns them all	off.

       When upsmon runs	as a secondary,	it is relying on the distant system to
       tell it about the state of the UPS. When	that UPS goes critical (on
       battery and low battery), it immediately	invokes	the local shutdown
       command.	This needs to happen quickly. Once all secondaries disconnect
       from the	distant	upsd(8)	server,	its primary-mode upsmon	will start its
       own shutdown process. Your secondary systems must all quiesce and shut
       down before the primary turns off the shared power source, or
       filesystem damage may result.

       upsmon deals with secondaries that get wedged, hang, or otherwise fail
       to disconnect from upsd(8) in a timely manner with the HOSTSYNC timer.
       During a	shutdown situation, the	primary	upsmon will give up after this
       interval	and it will shut down anyway. This keeps the primary from
       sitting there forever (which would endanger that	host) if a secondary
       should break somehow. This defaults to 15 seconds.

       If your primary system is shutting down too quickly, set	the FINALDELAY
       interval	to something greater than the default 15 seconds. Don't	set
       this too	high, or your UPS battery may run out of power before the
       primary upsmon process shuts down that system.

TIMED SHUTDOWNS
       For those rare situations where the shutdown process can't be completed
       between the time	that low battery is signalled and the UPS actually
       powers off the load, use	the upssched(8)	helper program.	You can	use it
       along with upsmon to schedule a shutdown	based on the "on battery"
       event. upssched can then	come back to upsmon to initiate	the shutdown
       once it has run on battery too long.

       This can	be complicated and messy, so stick to the default critical UPS
       handling	if you can.

REDUNDANT POWER	SUPPLIES
       If you have more	than one power supply for redundant power, you may
       also have more than one UPS feeding your	computer. upsmon can handle
       this. Be	sure to	set the	UPS power values appropriately and the
       MINSUPPLIES value high enough so	that it	keeps running until it really
       does need to shut down.

       For example, the	HP NetServer LH4 by default has	3 power	supplies
       installed, with one bay empty. It has two power cords, one per side of
       the box.	This means that	one power cord powers two power	supply bays,
       and that	you can	only have two UPSes supplying power.

       Connect UPS "alpha" to the cord feeding two power supplies, and UPS
       "beta" to the cord that feeds the third and the empty slot. Define
       alpha as	a powervalue of	2, and beta as a powervalue of 1. Set the
       MINSUPPLIES to 2.

       When alpha goes on battery, your	current	overall	power value will stay
       at 3, as	it's still supplying power. However, once it goes critical (on
       battery and low battery), it will stop contributing to the current
       overall power value. That means the value will be 1 (beta alone), which
       is less than 2. That is insufficient to run the system, and upsmon will
       invoke the shutdown sequence.

       However,	if beta	goes critical, subtracting its contribution will take
       the current overall value from 3	to 2. This is just high	enough to
       satisfy the minimum, so the system will continue	running	as before. If
       beta returns later, it will be re-added and the current value will go
       back to 3. This allows you to swap out UPSes, change a power
       configuration, or whatever, as long as you maintain the minimum power
       value at	all times.

MIXED OPERATIONS
       Besides being able to monitor multiple UPSes, upsmon can	also monitor
       them as different roles.	If you have a system with multiple power
       supplies	serviced by separate UPS batteries, it's possible to be	a
       primary on one UPS and a	secondary on the other.	This usually happens
       when you	run out	of serial or USB ports and need	to do the monitoring
       through another system nearby.

       This is also complicated, especially when it comes time to power	down a
       UPS that	has gone critical but doesn't supply the local system. You can
       do this with some scripting magic in your notify	command	script,	but
       it's beyond the scope of	this manual.

FORCED SHUTDOWNS
       When upsmon is forced to	bring down the local system, it	sets the "FSD"
       (forced shutdown) flag on any UPSes that	it is running in primary mode.
       This is used to synchronize secondary systems in	the event that a
       primary which is	otherwise OK needs to be brought down due to some
       pressing	event on the UPS manager system.

       You can manually	invoke this mode on the	system with primary-mode
       upsmon by starting another copy of the program with -c fsd command line
       argument. This is useful	when you want to initiate a shutdown before
       the critical stage through some external	means, such as upssched(8).

DEAD UPSES
       In the event that upsmon	can't reach upsd(8), it	declares that UPS
       "dead" after some interval controlled by	DEADTIME in the
       upsmon.conf(5). If this happens while that UPS was last known to	be on
       battery,	it is assumed to have gone critical and	no longer contributes
       to the overall power value.

       upsmon will alert you to	a UPS that can't be contacted for monitoring
       with a "NOCOMM" notifier	by default every 300 seconds. This can be
       changed with the	NOCOMMWARNTIME setting.

RELOADING NUANCES
       upsmon usually gives up root powers for the process that	does most of
       the work, including handling signals like SIGHUP	to reload the
       configuration file. This	means your upsmon.conf(8) file must be
       readable	by the non-root	account	that upsmon switches to.

       If you want reloads to work, upsmon must	run as some user that has
       permissions to read the configuration file. I recommend making a	new
       user just for this purpose, as making the file readable by "nobody"
       (the default user) would	be a bad idea.

       See the RUN_AS_USER section in upsmon.conf(8) for more on this topic.

       Additionally, you can't change the SHUTDOWNCMD or POWERDOWNFLAG
       definitions with	a reload due to	the split-process model. If you	change
       those values, you must stop upsmon and start it back up.	upsmon will
       warn you	in the syslog if you make changes to either of those values
       during a	reload.

SIMULATING POWER FAILURES
       To test a synchronized shutdown without pulling the plug	on your
       UPS(es),	you need only set the forced shutdown (FSD) flag on them. You
       can do this by calling upsmon again to set the flag, i.e.:

       upsmon -c fsd

       After that, the primary and the secondary will do their usual shutdown
       sequence	as if the battery had gone critical, while you can time	how
       long it takes for them. This is much easier on your UPS equipment, and
       it beats	crawling under a desk to find the plug.

       Note you	can also use a dummy SHUTDOWNCMD setting to just report	that
       the systems would shut down at this point, without actually disrupting
       their work.

FILES
       upsmon.conf(5)

SEE ALSO
   Server:
       upsd(8)

   Clients:
       upsc(8),	upscmd(8), upsrw(8), upsmon(8)

   CGI programs:
       upsset.cgi(8), upsstats.cgi(8), upsimage.cgi(8)

   Internet resources:
       The NUT (Network	UPS Tools) home	page: http://www.networkupstools.org/

Network	UPS Tools 2.7.4.	  11/05/2021			     UPSMON(8)

NAME | SYNOPSIS | DESCRIPTION | OPTIONS | UPS DEFINITIONS | NOTIFY EVENTS | NOTIFY COMMAND | NOTIFY FLAGS | NOTIFY MESSAGES | POWER VALUES | UPS TYPES | TIMED SHUTDOWNS | REDUNDANT POWER SUPPLIES | MIXED OPERATIONS | FORCED SHUTDOWNS | DEAD UPSES | RELOADING NUANCES | SIMULATING POWER FAILURES | FILES | SEE ALSO