Skip site navigation (1)Skip section navigation (2)

FreeBSD Manual Pages

  
 
  

home | help
mAM001(3)		     One-Wire File System		     mAM001(3)

NAME
       mAM001 -	Analog Input Module

SYNOPSIS
   Voltage or current meter.
       B2 [.]XXXXXXXXXXXX[XX][/[ current | volts | address | crc8 | id | loca-
       tor | r_address | r_id |	r_locator | type ]]

FAMILY CODE
       B2

SPECIAL	PROPERTIES
       Note that the volts and current	are  mutually  exclusive  and  set  by
       switches	on the sensor case.

       Although	 both volts and	current	will give a value, only	one of the two
       is correct. (Based on the electrical connections	and switch settings).

   current
       read-write, floating point
       Reads the current.

       Range  0-20mA

       Resolution
	      12 bit (5	uA)

       Units  A	(amperes)

       Frequency
	      DC

   volts
       read-write, floating point
       Reads the voltage.

       Range  0-10V

       Resolution
	      12 bit (2.5 mV)

       Units  V	(volts)

       Frequency
	      DC

STANDARD PROPERTIES
   address
   r_address
       read-only, ascii
       The entire 64-bit unique	ID. Given as  upper  case  hexidecimal	digits
       (0-9A-F).
       address starts with the family code
       r address is the	address	in reverse order, which	is often used in other
       applications and	labeling.

   crc8
       read-only, ascii
       The 8-bit error correction portion. Uses	cyclic redundancy check.  Com-
       puted  from the preceding 56 bits of the	unique ID number. Given	as up-
       per case	hexadecimal digits (0-9A-F).

   family
       read-only, ascii
       The 8-bit family	code. Unique to	each type of device.  Given  as	 upper
       case hexadecimal	digits (0-9A-F).

   id
   r_id
       read-only, ascii
       The 48-bit middle portion of the	unique ID number. Does not include the
       family code or CRC. Given as upper case hexadecimal digits (0-9A-F).
       r id is the id in reverse order,	which is often used in other  applica-
       tions and labeling.

   locator
   r_locator
       read-only, ascii
       Uses  an	 extension  of the 1-wire design from iButtonLink company that
       associated 1-wire physical connections with a unique  1-wire  code.  If
       the  connection is behind a Link	Locator	the locator will show a	unique
       8-byte number (16 character hexadecimal)	starting with family code FE.
       If no Link Locator is between the device	and the	 master,  the  locator
       field will be all FF.
       r locator is the	locator	in reverse order.

   present (DEPRECATED)
       read-only, yes-no
       Is the device currently present on the 1-wire bus?

   type
       read-only, ascii
       Part  name  assigned by Dallas Semi. E.g.  DS2401 Alternative packaging
       (iButton	vs chip) will not be distiguished.

ALARMS
       None.

DESCRIPTION
   1-Wire
       1-wire is a wiring protocol and series of devices designed and manufac-
       tured  by  Dallas  Semiconductor, Inc. The bus is a low-power low-speed
       low-connector scheme where the data line	can also provide power.

       Each device is uniquely and unalterably	numbered  during  manufacture.
       There  are a wide variety of devices, including memory, sensors (humid-
       ity, temperature, voltage, contact, current), switches, timers and data
       loggers.	 More complex devices (like thermocouple sensors) can be built
       with these basic	devices. There are also	1-wire devices that  have  en-
       cryption	included.

       The  1-wire  scheme uses	a single bus master and	multiple slaves	on the
       same wire. The bus master initiates all communication. The  slaves  can
       be individually discovered and addressed	using their unique ID.

       Bus  masters come in a variety of configurations	including serial, par-
       allel, i2c, network or USB adapters.

   OWFS	design
       OWFS is a suite of programs that	designed to make the  1-wire  bus  and
       its  devices easily accessible. The underlying principle	is to create a
       virtual filesystem, with	the unique ID being the	directory, and the in-
       dividual	 properties of the device are represented as simple files that
       can be read and written.

       Details of the individual slave or master design	are  hidden  behind  a
       consistent interface. The goal is to provide an easy set	of tools for a
       software	designer to create monitoring or control  applications.	 There
       are some	performance enhancements in the	implementation,	including data
       caching,	parallel access	to bus masters,	and aggregation	of device com-
       munication.  Still the fundamental goal has been	ease of	use, flexibil-
       ity and correctness rather than speed.

   mAM001
       The mAM001 (3) is a voltage or current meter from CMC Industrial	 Elec-
       tronics.	It is packaged for industrial use.

ADDRESSING
       All  1-wire  devices are	factory	assigned a unique 64-bit address. This
       address is of the form:

       Family Code
	      8	bits

       Address
	      48 bits

       CRC    8	bits

       Addressing under	OWFS is	in hexadecimal,	of form:

	      01.123456789ABC

       where 01	is an example 8-bit family code, and 12345678ABC is an example
       48 bit address.

       The  dot	 is  optional,	and the	CRC code can included. If included, it
       must be correct.

WEBSITE
       http://www.cmciel.com/products-solutions/individual-products/analog-in-
       put-mam001/

SEE ALSO
   Programs
       owfs  (1)  owhttpd  (1)	owftpd	(1)  owserver (1) owdir	(1) owread (1)
       owwrite (1) owpresent (1) owtap (1)

   Configuration and testing
       owfs (5)	owtap (1) owmon	(1)

   Language bindings
       owtcl (3) owperl	(3) owcapi (3)

   Clocks
       DS1427 (3) DS1904 (3) DS1994 (3)	DS2404	(3)  DS2404S  (3)  DS2415  (3)
       DS2417 (3)

   ID
       DS2401 (3) DS2411 (3) DS1990A (3)

   Memory
       DS1982  (3)  DS1985  (3)	 DS1986	 (3)  DS1991 (3) DS1992	(3) DS1993 (3)
       DS1995 (3) DS1996 (3) DS2430A (3) DS2431	 (3)  DS2433  (3)  DS2502  (3)
       DS2506 (3) DS28E04 (3) DS28EC20 (3)

   Switches
       DS2405 (3) DS2406 (3) DS2408 (3)	DS2409 (3) DS2413 (3) DS28EA00 (3)

   Temperature
       DS1822  (3)  DS1825  (3)	 DS1820	(3) DS18B20 (3)	DS18S20	(3) DS1920 (3)
       DS1921 (3) DS1821 (3) DS28EA00 (3) DS28E04 (3) EDS0064 (3) EDS0065  (3)
       EDS0066	(3)  EDS0067  (3) EDS0068 (3) EDS0071 (3) EDS0072 (3) MAX31826
       (3)

   Humidity
       DS1922 (3) DS2438 (3) EDS0065 (3) EDS0068 (3)

   Voltage
       DS2450 (3)

   Resistance
       DS2890 (3)

   Multifunction (current, voltage, temperature)
       DS2436 (3) DS2437 (3) DS2438 (3)	 DS2751	 (3)  DS2755  (3)  DS2756  (3)
       DS2760 (3) DS2770 (3) DS2780 (3)	DS2781 (3) DS2788 (3) DS2784 (3)

   Counter
       DS2423 (3)

   LCD Screen
       LCD (3) DS2408 (3)

   Crypto
       DS1977 (3)

   Pressure
       DS2406 (3) TAI8570 (3) EDS0066 (3) EDS0068 (3)

   Moisture
       EEEF (3)	DS2438 (3)

AVAILABILITY
       http://www.owfs.org

AUTHOR
       Paul Alfille (paul.alfille@gmail.com)

OWFS Manpage			     2003			     mAM001(3)

NAME | SYNOPSIS | FAMILY CODE | SPECIAL PROPERTIES | STANDARD PROPERTIES | ALARMS | DESCRIPTION | ADDRESSING | WEBSITE | SEE ALSO | AVAILABILITY | AUTHOR

Want to link to this manual page? Use this URL:
<https://www.freebsd.org/cgi/man.cgi?query=mAM001&sektion=3&manpath=FreeBSD+12.1-RELEASE+and+Ports>